How-to
Connecting SCADA to an S7-300 MPI port with a PC adapter USB
Short answer
Use the Siemens PC Adapter USB (6ES7972-0CB20-0XA0) between the SCADA PC's USB port and the S7-300's MPI port, set the network to the MPI default of 187.5 kbps and point your SCADA's OPC server or native driver at the CPU's MPI address. A generic RS-232 to RS-485 converter cannot work because MPI is a Siemens protocol, not plain RS-485.

On this page
The direct answer: for a serial SCADA connection to an S7-300's MPI port, buy the Siemens PC Adapter USB, part number 6ES7972-0CB20-0XA0, plug its USB side into the SCADA workstation and its 9-pin RS-485 side into the CPU's MPI port, and set the network to the MPI default of 187.5 kbps. There is no way to do it with a bare RS-232-to-RS-485 converter, because MPI is Siemens' own protocol riding on RS-485 wiring, and the converter does not speak it. A USB route works, and the same adapter serves both your programming tool and the SCADA runtime.
What MPI actually is and why the converter fails #
The Multi-Point Interface on an S7-300 CPU is an RS-485 electrical interface carrying Siemens' MPI protocol. The wiring is two conductors and a shield, which is why the plug physically accepts an ordinary PROFIBUS or RS-485 cable. But the frames on it are MPI frames: token passing between stations, connection setup, S7 read and write services. A generic RS-232-to-RS-485 converter only shifts voltage levels between a COM port and the bus; it has no MPI protocol stack, so the CPU never answers it. This is the same port-sharing problem described in the article on why an S7-200 cannot share one RS-485 port with a PC and Modbus: two different protocols cannot share one RS-485 interface just because the pins match.
The PC Adapter USB contains that protocol stack. The Siemens manual rates it at up to 1.5 Mbps on the MPI/DP network, and the S7-300 CPU documentation lists 187.5 kbps as the default baud rate for all CPUs, with 19.2 kbps used when talking to an S7-200. Set the rate to that default and both sides agree.
Steps to connect the adapter and SCADA #
-
Install the adapter driver from your STEP 7 installation media on the SCADA workstation. Check in Device Manager that the adapter enumerates as a USB serial device before going further.
-
Set the adapter's interface properties to the network you are on: MPI, not PROFIBUS or PPI, and the baud rate to the MPI default. That default matches a CPU you have not changed. (If your project runs a lower rate, the driver named PC.Adapter.MPI only operates at 19.2 kbps and the default rate on ports 0 and 1, so nothing between those two values is available.)
-
Wire the adapter's 9-pin connector to the CPU's MPI connector with a PROFIBUS cable, and terminate both ends of the segment. The adapter takes its 24 V supply through that same connector, so on a bench with no powered CPU you must feed the connector from a 24 V source or the adapter will not communicate.
-
Note the CPU's MPI address, configured in STEP 7 under the CPU's interface properties. The usual station address is 2; your adapter and the SCADA driver must use a different address on the same network, and the driver must target the CPU's address.
-
In the SCADA software, create a channel through an OPC server such as Simatic Net, which exposes the MPI adapter as a data source, or through the SCADA package's own Siemens S7 driver configured to use that adapter. WinCC talks to MPI natively; packages such as LabVIEW's DSC module or LookOut reach MPI through an OPC server instead. The S7-1500 connection described in the article on connecting a CODESYS HMI on Windows to an S7-1500 PLC works differently because that CPU speaks Ethernet natively; with MPI you are tied to the adapter driver.
-
Read one value, verify it, then scale up the tag list.
If the adapter installs but will not talk, the driver and cable faults behind that symptom are covered in the guide on resolving USB MPI adapter driver errors and the one on troubleshooting a USB MPI adapter that is not communicating; both apply directly to this connection.
Worked example: what the default rate buys you #
Suppose your SCADA polls one block of 100 holding words (200 bytes) plus roughly 30 bytes of MPI transaction overhead per read. At 187.5 kbps with 8 bits per byte, the wire carries 23,437.5 bytes per second. One transaction of 230 bytes therefore occupies about 230 / 23,437.5 = 9.8 ms. Polling that block ten times a second consumes about 98 ms of wire time per second, which leaves ample headroom for an HMI and a programming station sharing the network.
Now run the same arithmetic at 19.2 kbps: 2,400 bytes per second, so the same 230-byte transaction takes about 230 / 2,400 = 95.8 ms, and ten polls per second consume nearly a second of wire time per second, which does not fit. That is the whole case for holding the network at the default rate. This example assumes one master transaction at a time and the overhead above; your frame sizes move the numbers, but not the conclusion.
When to choose a different route #
If the tag count or update rate outgrows serial MPI, the right move is Ethernet: add a communications processor to the rack and serve the SCADA from it, as covered in the article on S7-300 Modbus TCP and the CPU serial number registration. Ethernet also frees the MPI port for programming. When you specify or replace the computer that runs the SCADA client and OPC server at the machine, an industrial panel PC is the form that survives cabinet-door and console duty; the driver and adapter steps above are identical on it.
One safety note: commission the connection with the process in a safe state. Setting an MPI address or baud rate on a CPU can drop an existing HMI connection, and on a running line that lost link can leave operators blind.
The decision, in one line per case: new serial SCADA connection to an S7-300 MPI port — PC Adapter USB 6ES7972-0CB20-0XA0 at the MPI default rate through an OPC server or native driver; any proposal involving a plain RS-232-to-RS-485 converter — reject it, the protocol will not pass; a network that must include an S7-200 — 19.2 kbps on that segment; hundreds of fast tags — add an Ethernet communications processor instead of pushing MPI harder.
Questions asked
Can a generic RS-232 to RS-485 converter connect SCADA to an S7-300 MPI port?
No. MPI runs over RS-485 wiring, but the bytes on the wire follow Siemens' MPI protocol, which a generic converter does not understand. It will change the electrical levels and nothing else. You need an adapter that implements the MPI protocol stack, such as the PC Adapter USB 6ES7972-0CB20-0XA0, or an Ethernet path with a communications processor in the rack.
What baud rate should the MPI network run at for SCADA polling?
Leave the S7-300 MPI network at its default of 187.5 kbps unless another device on it forces a lower rate. The PC Adapter USB supports up to 1.5 Mbps, so it is not the limiting factor. If you must talk to an S7-200 on the same network, drop that segment to 19.2 kbps; the adapter driver named PC.Adapter.MPI supports only 19.2 kbps and the normal MPI rate, so nothing in between is usable.
Does the PC Adapter USB need an external power supply?
Yes, and usually you never notice it: the adapter draws 24 V from the MPI or PROFIBUS connector, which the CPU's interface provides. On a bench setup with no CPU or an unpowered network, the adapter has no supply, so it will enumerate on USB but not communicate. Feed the connector from a 24 V source in that case.
Is serial MPI fast enough for a SCADA system, or do I need Ethernet?
It depends on your poll volume. At 187.5 kbps a transaction that moves a couple hundred bytes takes on the order of 10 ms, which suits alarm and status polling of tens of tags per second. If you trend hundreds of tags or need update times under 100 ms across the whole station, add a communications processor such as a CP 343-1 to the rack and use ISO-on-TCP or S7 connections over Ethernet instead.