IMDHMIControls LibraryShop main store

How-to

Connecting MicroLogix 1200 PLCs to SCADA through a Net-ENI

Industrial networks Published 8 min read

Short answer

Yes, you can leave each MicroLogix 1200 untouched when its Channel 0 already runs DF1 full-duplex, because the 1761-NET-ENI speaks DF1 on its serial side; only a controller configured for DH-485 needs RSLogix 500 to switch the channel and a redownload. Give each Net-ENI a unique Ethernet endpoint and bind each InTouch tag group to its own controller path.

On this page
  1. Do you have to change the MicroLogix 1200 port configuration?
  2. How do you check which protocol the port uses?
  3. Do you need RSLogix 500 to do this?
  4. How is the Net-ENI wired to the controller?
  5. How do you set up three Net-ENIs on one Ethernet?
  6. How do the InTouch tags reach each controller?
  7. How many tags can one Net-ENI path carry?
  8. How do you commission and verify the whole path?
  9. Questions asked

Yes, you can put three MicroLogix 1200 controllers on centralized Wonderware InTouch with one 1761-NET-ENI each, and the port-change question has a clean answer: a controller whose Channel 0 already runs DF1 full-duplex needs nothing touched inside the PLC, because the Net-ENI speaks DF1 on its serial side; a controller still set for DH-485 needs RSLogix 500, a channel edit to DF1, and a download. Read the setting before you buy or wire anything, then give each module a unique Ethernet endpoint and bind each tag group to its own path. This article walks the conversion in that order, with the arithmetic that shows the serial link is not the bottleneck.

Do you have to change the MicroLogix 1200 port configuration? #

Not when Channel 0 already runs DF1 full-duplex, because the 1761-NET-ENI terminates the Ethernet connection on one side and exchanges DF1 messages on the other; only a controller left configured for DH-485 needs a channel edit and a project download.

Publication 1761-UM006, the user manual for these modules, documents the 1761-NET-ENI and 1761-NET-ENIW as EtherNet/IP interfaces for MicroLogix and CompactLogix controllers and for other DF1 full-duplex devices. The module owns the Ethernet conversation and carries DF1 over RS-232 to whatever sits on its serial cable, so the protocol decision lands entirely on the controller's Channel 0.

That boundary matters in troubleshooting too. A module that answers on Ethernet proves only that the module is alive: if the controller port is still on DH-485, the serial conversation never starts, and every tag on that endpoint reads bad while the module itself looks healthy.

Treat the three controllers as three separate readings. That three PanelView 550 terminals were installed the same way is not evidence that three channel configurations match — classify each port from its own project before wiring anything.

How do you check which protocol the port uses? #

Open the serial channel configuration in the controller project — online through a working connection or from the saved file — and read the protocol field; the PanelView 550 model number alone cannot settle it, because both DF1 and DH-485 were valid point-to-point choices.

DH-485 also appears as a multi-drop network linking several controllers, but that difference does not change this check. Classify each of the three controllers and act by row:

What Channel 0 says What you do Controller download
DF1 full-duplex Leave the port alone; wire the module onto it None
DH-485 Edit the channel to DF1 full-duplex in RSLogix 500 One, in a planned stop
Unknown Stop and identify the protocol before connecting the module —

Record the remaining channel settings at the same time — baud and DF1 station address — so a working DF1 port is never disturbed for the sake of uniformity. A known-good configuration is worth more than a tidy one.

Do you need RSLogix 500 to do this? #

You need it only for the DH-485 case: one licensed engineering workstation edits each DH-485 channel to DF1 and downloads the project, while DF1 controllers need no PLC software at all for the conversion.

For a controller already on DF1, the module takes the PanelView's place on the same port and speaks the protocol already there. A license bought for those controllers buys nothing.

For each DH-485 controller, one licensed workstation makes the change: set the serial channel to DF1 full-duplex, download, and confirm the controller returns to RUN. Record the original channel settings first and keep the pre-change project copy labeled by controller — that file is the rollback path. If the plant holds no licensed copy, obtaining RSLogix 500 through official licensing channels is the legitimate route, or a service provider with a licensed workstation makes the edit while the project documentation stays with the machine.

Schedule each download for a stop window: loading a project takes the controller out of RUN, and everything it drives sits at its de-energized state until the load finishes. After the change, the programming computer's own route to that controller is the DF1 serial link — the removed PanelView path is no longer a fallback for testing.

How is the Net-ENI wired to the controller? #

Connect the module's RS-232 port to the MicroLogix 1200 serial port with a 1761-CBL-PM02 cable — a 2 m null modem — after removing the PanelView 550, since this controller has exactly one serial port and the module takes its place.

On the module side the serial connection is a DB-9, on the controller side it is the port the PanelView occupied, and the module takes its power from a DC supply. DF1 full-duplex runs with no handshaking, so there are no modem control lines to sort out: the physical layer is one cable and one power feed.

How do you set up three Net-ENIs on one Ethernet? #

Give each module its own unique Ethernet endpoint with the ENI configuration utility and write down the endpoint-to-controller mapping before touching Wonderware, because every InTouch tag reaches its controller only through that one endpoint.

The utility ships with the package documented in publication 1761-UM006, and it configures the module itself — nothing on the controller side changes to make the endpoint exist. An illustrative assignment: 192.168.1.101 to the first module, 192.168.1.102 to the second, 192.168.1.103 to the third, each written against its controller and process area. The addresses themselves are yours to choose within your plant's plan; the requirements are uniqueness and a map that outlives the commissioning.

How do the InTouch tags reach each controller? #

Configure the Wonderware communications driver once per endpoint, then bind each tag group to the access name that points at that endpoint, so tag quality follows one controller path instead of three mixed ones.

In practice that means one access name per endpoint and item names that resolve through it to data table addresses in that controller. The failure pattern tells you where to look: all tags from one controller bad points at that endpoint path — module power, cable, endpoint, access name — while all tags from all three bad at once points at the Wonderware side first, because three independent serial links rarely fail in the same minute.

Pick one address per controller that changes on its own, such as a timer or counter accumulator, and carry it through commissioning as the reference value.

How many tags can one Net-ENI path carry? #

An illustrative run at 19200 bit/s puts the ceiling near 80 small reads per second, so 15 tags polled once per second load that link under 19 percent — the serial side is rarely the limit.

Worked example, illustrative inputs: take the serial side at 19200 bit/s, reading your actual baud off the channel screen rather than assuming it. A 10-bit character frame — one start, eight data, one stop, no parity — gives 19200 bit/s ÷ 10 bits/character = 1920 characters per second. A small typed read plus its reply is on the order of 24 characters round trip, so the ceiling is 1920 ÷ 24 = 80 transactions per second. Polling 15 tags once a second on one controller uses 15 × 24 = 360 characters per second = 3600 bit/s, which is 3600 ÷ 19200 = 18.75 percent of the line.

Each controller has its own module and its own serial link, so this is a per-controller number, not a combined one. Even at double the frame estimate — 48 characters round trip — the ceiling is still 40 transactions per second, above a one-second poll of 15 tags.

This is framing arithmetic, not a measured benchmark, but the decision it gives is robust: at dozens of tags and a one-second poll, the DF1 link holds roughly five times headroom. Only a controller whose read demand exceeds that ceiling has a serial constraint, and the fixes are a slower poll class for non-critical tags or a higher baud setting — not a second module.

How do you commission and verify the whole path? #

Bring one controller up end to end first — port setting, cable, endpoint, driver, tags — then duplicate that working pattern to the other two, because commissioning three at once hides whether a fault is common configuration or one controller's port.

  1. Back up each controller's project while the old connection still works, and label the files by controller.
  2. Read each Channel 0 configuration and record protocol, baud, and DF1 station address; classify each controller DF1 or DH-485.
  3. Leave DF1 controllers untouched. For a DH-485 controller, set the channel to DF1 full-duplex in RSLogix 500 and download during the planned stop, original project copy in hand.
  4. Remove the PanelView 550 cable and land the 1761-CBL-PM02 between the module's RS-232 port and the controller port; power the module.
  5. Set that module's unique Ethernet endpoint with the ENI configuration utility and add it to the written map.
  6. Add the Wonderware driver path for that endpoint and bind the tag group's access name to it.
  7. Verify outward from the controller: watch the reference address change at the controller, then confirm the module's endpoint answers on Ethernet.
  8. Verify inward from the screen: the matching tag shows good quality and tracks the reference value; write once to a non-critical address to prove the write path.
  9. Repeat for the second and third controller, one at a time, until all three run.
  10. File the endpoint map and the before-and-after channel settings with the panel documentation.

Questions asked

Does the MicroLogix 1200 get an IP address when you add the Net-ENI?

No. The controller keeps only its ordinary DF1 station address; the IP endpoint lives entirely in the Net-ENI. That is why the port setting you are inspecting is a serial protocol choice, not a network setting, and why nothing in the MicroLogix project has to carry addressing for Wonderware to find the controller.

Can one Net-ENI serve more than one MicroLogix?

Not on the serial side. The module exchanges DF1 full-duplex over a point-to-point RS-232 link, so it converses with one controller at a time, which makes three modules with three endpoints the correct architecture for three controllers. If that is a constraint, the alternative is a controller with native Ethernet, not one shared module.

Reads work but writes to the PLC fail — is that the port configuration?

Almost never. Reads and writes cross the same DF1 path, so a protocol mismatch would break both. Work outward: confirm the tag's access mode permits writes, confirm the item name and data type match the address, and confirm the controller is in a state that accepts a write. Only after those check out does the module's serial link enter the question.

Are 1761-NET-ENI modules still manufactured?

Allen-Bradley has discontinued the 1761-NET-ENI. Working units remain common in the installed base, and drop-in replacements exist for the same DF1 role, such as the 515RTAENI for legacy DF1 MicroLogix and SLC 5/03 connections. If you standardize on this architecture, decide spare coverage or a named replacement at commissioning, not after a failure.

Keep reading

  • Troubleshooting

    Reaching PLC-5 and SLC 500 data through a ControlLogix DH+ bridge

    Yes. An OPC UA server reaches PLC-5 and SLC 500 processors through a ControlLogix Ethernet-to-DH+ bridge when its Allen-Bradley driver documents routed legacy access. Confirm the driver, inventory the bridge modules, build each connection path to the DH+ node, and prove one read — the 1756-DHRIO carries 32 connections per DH+ channel.

    Industrial networks

  • Selection guide

    Connecting SLC 500 processors to Ignition SCADA

    For a serial-only SLC 5/03 that already feeds a PanelView, put a DF1-capable serial gateway with Ethernet upstream on the serial line and let Ignition share it in DF1 full-duplex. Swap in a 5/05 when the machine is due processor work anyway, because Ignition then gets a dedicated Ethernet channel. Use RSLinx Classic OPC-DA as a pilot when it is already licensed, and skip the DeviceNet-plus-LabVIEW route.

    Industrial networks

  • Troubleshooting

    MicroLogix 1000 not found in RSLinx after a channel change

    The MicroLogix 1000 is missing from RSLinx because the channel-configuration download changed its serial port from DF-1 to DH-485, so the DF-1 driver and Auto-Configure can never verify against it. Reach the controller through DH-485 with a 1747-UIC at its default 19200 baud, go online, set Channel Configuration back to DF-1, download, and re-run Auto-Configure.

    Industrial networks