How-to
Connecting a WAGO 750-354 EtherCAT coupler to ctrlX CORE
Short answer
Install WAGO_750-0354_22.xml in Tools > Device Repository, scan the 750-354 under ethercatmaster, transfer the fieldbus configuration, rescan for the 750 modules, then bind Data Layer channels such as Output_s_.Channel_1_Data_1 to PLC variables through DataLayer_Realtime.

On this page
A WAGO I/O System 750 stack talks to a ctrlX CORE through the 750-354 EtherCAT fieldbus coupler, and the whole setup is two scans, two configuration transfers and one Data Layer binding. The documented baseline is ctrlX CORE V1.10, the EtherCAT Master App V1.10, ctrlX I/O Engineering V1.10 and ctrlX PLC Engineering V1.10, with the description file WAGO_750-0354_22.xml and an example stack of a 750-354 coupler, 750-430 digital input, 750-530 digital output, 750-559 analog output, 750-468 analog input and 750-600 end module. Treat that stack as the example, not a requirement: your scanned modules must match the physical stack you actually assembled. If your field devices are IP67 blocks instead of 750 rail modules, the generic block setup is covered in the article on setting up IP67 EtherCAT remote I/O modules on a soft PLC.
Build the EtherCAT configuration #
- Open the ctrlX CORE web interface and add the EtherCAT master by clicking [+] under EtherCAT > Configuration, then confirm with OK.
- Click [ctrlX I/O Engineering] to launch the locally installed tool, choose a project name and a save folder, and if the project synchronization window appears choose [Use project from ctrlX].
- Install the description file via Tools > Device Repository… : click [Install], select WAGO_750-0354_22.xml (download it from the WAGO website, searching for 750), then [Close].
- Right-click ethercatmaster and choose Scan for Devices… . Click
Insert all newly scanned devicesand close with [OK]; the 750-354 Fieldbus Coupler EtherCAT now sits in the tree. - Select ethercatmaster and set State machine > Master state after download to Pre-OP, then choose Transferring field bus configuration from its context menu. Confirm the requested change to Init with [Yes].
With the coupler configured, scan a second time so the master sees the modules downstream of it:
- Choose Scan for Devices… again from ethercatmaster, click
Insert all newly scanned devicesand confirm with [OK]. The 750-430, 750-530, 750-559 and 750-468 appear as children of the coupler. - Set State machine > Master state after download to OP and run Transferring field bus configuration once more, confirming the change to Init with [Yes]. OP is the state that starts data cycling automatically after the transfer.
- Save with File > Save and exit ctrlX I/O Engineering.
- Check the fieldbus in the web interface under EtherCAT > Status. Do not touch PLC mapping while this page does not show a running configuration.
Verify the process data path #
A successful scan proves the topology, not the data. Prove the signal path with a loopback before writing any logic:
- Bridge digital outputs one and two to digital inputs one and two in hardware.
- Open System > Data Layer and find the output module
_750_5xx_750_15xx_8b_outand the input module_750_4xx_750_14xx_8b_in. - Override
Output_s_.Channel_1_Data_1andOutput_s_.Channel_2_Data_1manually and read backInput_s_.Channel_1_Data_1andInput_s_.Channel_2_Data_1.
Each bridged input must follow its output. If it does not, check the physical bridge first, then the channel selection, the EtherCAT state and the Data Layer item names; only then look at the PLC side. If the coupler enumerates but no I/O moves at all, the article on resolving no I/O response on a WAGO 750-354 EtherCAT coupler covers that failure on another controller, and the causes transfer.
Bind the channels to PLC variables #
- Launch ctrlX PLC Engineering from the web interface, create a project and pick a folder.
- In the Devices window, right-click DataLayer_Realtime and choose Edit > Online from ctrlX CORE… .
- Select
ethercat_master_instances_ethercatmaster, then the_750_354item, then all module items, clicking [Apply changes] at each step; select all channel items and close the dialog. - Double-click PLC_PRG (PRG). In the example, declare inputs
bInStartandbInStopas BOOL and map them to the first two channels of the input module; declare outputsbOutErrorandbOutReadyas BOOL and map them to the first two channels of the output module. - Log in with Online > Login, install the controller certificate with [OK], confirm application creation with [Yes], and start the program with Debug > Start.
Online mode now shows live values; forcing bInStop in the PLC changes the corresponding output channel, and you can watch it arrive on the bridged input. Save with File > Save.
Special modules #
Plain digital and analog modules run on process data alone. Two families do not:
- 753-647 DALI Multi-Master: connect a PC through the coupler's serial service port with the 750-923 cable, configure lines and groups with the WAGO DALI Configurator and switch the module to easy mode; DALI devices are then controlled through EtherCAT process data. Transparent or full mode needs WAGO function blocks documented for CODESYS V2.3 and e!COCKPIT, not for ctrlX PLC Engineering, so design around easy mode there.
- 750-652 serial and 753-649 M-Bus: use the WAGO libraries WagoAppCom and WagoAppM-Bus respectively, and confirm the current library release names your ctrlX PLC Engineering version before committing the design.
One safety note: everything above is standard I/O on a standard master. No 750 module configured this way performs a safety function, so guard interlocks still need a certified safety device, not a bridged input in the Data Layer.
The decision: for ordinary 750 digital and analog I/O on ctrlX CORE, run the two-scan sequence above with Pre-OP before the first transfer and OP before the second, loopback-test the channels, and bind through DataLayer_Realtime. For IO-Link sensors instead of 750 modules, the routing steps differ and are covered in the article on routing an IO-Link master to a ctrlX CORE over EtherCAT.
Questions asked
Which device description file does the 750-354 need?
The documented example uses WAGO_750-0354_22.xml, installed through Tools > Device Repository in ctrlX I/O Engineering. Download it from the WAGO website by searching for 750, and use the file that matches your coupler and the EtherCAT Master App version in the installation; a mismatched description can leave the coupler scannable but without a valid module configuration.
Why does the master state change between Pre-OP and OP?
Pre-OP is selected before each transfer so the master does not exchange cyclic data while the topology is edited; the second transfer asks to drop to Init, which you confirm with Yes. After the final transfer the documented setup selects OP under State machine > Master state after download so data cycling begins automatically. Check the actual state under EtherCAT > Status in the ctrlX CORE web interface before trusting any process value.
Can a 753-647 DALI Multi-Master be used on this coupler?
Yes, in easy mode. Transparent or full mode needs WAGO function blocks that are documented for CODESYS V2.3 and e!COCKPIT, not for ctrlX PLC Engineering, so do not design around full DALI access there.
What about the 750-652 serial module and the 753-649 M-Bus master?
Both are supported through WAGO libraries rather than plain process data: WagoAppCom for the 750-652 and WagoAppM-Bus for the 753-649. Get the current library release from WAGO and confirm it lists your ctrlX PLC Engineering version before binding logic to those modules, because library support is version-dependent.