Explainer

CODESYS IO-Link SL target support limits on ctrlX CORE

PLC programming Published 6 min read

Short answer

No, CODESYS IO-Link SL (article no. 2303000008) is a single-device target license, and the ctrlX CORE does not currently provide it, so its scan-to-project, configurator and IODD.xml workflow cannot run on that controller. Add the IO-Link master over EtherCAT or PROFINET, read and write parameters acyclically, and manage the rest outside the project.

On this page
  1. What CODESYS IO-Link SL licenses
  2. The five functions the add-on provides
  3. Why the ctrlX CORE stops at the gate
  4. What the restriction is not
  5. The route that works on a ctrlX CORE today
  6. Worked example: an EtherCAT IO-Link master on a ctrlX CORE against the five functions
  7. The decision for each case
  8. Questions asked

No. CODESYS IO-Link SL is a single-device target license, and the ctrlX CORE does not currently provide it, so the integrated workflow you describe — sensors recognized in the device scan, direct import, configurators, parameters stored in the project, IODD.xml-based data processing — cannot run on that controller today. The gate is target support, and it sits ahead of every device-level setting: no IODD file, engineering package, or master firmware changes it. The route that works is an IO-Link master over EtherCAT or PROFINET with cyclic data and acyclic parameter access, with the workflow functions the add-on would have provided moved into your procedures. As of a March 2024 answer from the controller vendor, providing the license through ctrlX license management was under review.

CODESYS IO-Link SL, article no. 2303000008, is sold in the CODESYS Store under the Application-Based Licenses category, and it integrates IO-Link devices into CODESYS projects on EtherCAT and PROFINET bus systems. The license type is the whole story here: it is a single-device license, usable on the one target device or PLC on which the CODESYS runtime is installed. One controller, one license; the engineering PC is not what gets licensed.

CODESYS treats IO-Link capability as separately licensed SL components rather than a free part of the runtime — the same catalog contains CODESYS IO-Link Master (for EL6224) SL, a device-specific license for one EtherCAT IO-Link master terminal. On the ctrlX side, CODESYS functionality itself arrives through the controller's license management, the mechanism behind how the ctrlX PLC license calculates I/O data and core use, and that is the list IO-Link SL has to appear on before anything else can happen.

The five functions the add-on provides #

Its published description promises five things, and they make a usable acceptance yardstick for any substitute:

  • IO-Link sensors are recognized in the engineering device scan.
  • Discovered devices import directly into the project.
  • Configurators parameterize the IO-Link devices.
  • The device parameters are stored in the CODESYS project.
  • Sensor and actuator data is processed using the IODD.xml files.

Hold that list. When you evaluate an alternative, score it against these five, because a route that moves bytes reliably can still leave four of them behind.

Why the ctrlX CORE stops at the gate #

The ctrlX CORE exposes CODESYS as a licensed add-on under the controller's own license management, so a store article number only matters if the controller offers it. The vendor's support answer is direct: CODESYS IO-Link SL is a target license that the ctrlX CORE does not currently provide, and providing it through their license management was under review as of March 2024. Buying article 2303000008 anyway does not create an activation path — the single-device license activates on a runtime that provides it, through that vendor's mechanism.

Two practical consequences follow. First, the check that matters is the controller's license offering and its release notes, not the engineering software version on your PC. Second, the answer moves only with a controller release: re-check it before each new project, because "under review" is a status, not a promise.

What the restriction is not #

It is not a fieldbus choice: the add-on documents both EtherCAT and PROFINET as supported bus systems, and the refusal would be identical on either. It is not an IODD problem: an IODD.xml file describes one device's identity, parameters and data layout; it is not a runtime license, and it cannot be imported into a target that does not license the workflow. And it is not a sensor, port-mode, or master-firmware fault: those live downstream of a gate the controller never opened. Installing the engineering-side component or a stack of IODD files on the PC changes nothing on the target.

The route that works on a ctrlX CORE today #

Treat the IO-Link master as what it is on this controller: a fieldbus device whose ports happen to speak IO-Link. You can route an IO-Link master to a ctrlX CORE over EtherCAT, and each port's cyclic data lands in the process image as input and output bytes. Parameters stay reachable: you can read IO-Link parameters over EtherCAT AoE from a ctrlX PLC, or read IO-Link ISDU parameters over PROFINET acyclic record data when the master sits on that bus. On an EtherNet/IP controller, the equivalent door is configuring IO-Link ISDU access over CIP messaging.

Everything the add-on would have automated now belongs to you. Pull the process-data layout — lengths, field boundaries, scaling, signedness — out of the IODD.xml and code it; if port data arrives split into bits instead of whole bytes, look at the mapping in the master's device description first, the same fault pattern behind why ctrlX I/O Engineering shows bits instead of byte mapping nodes. If the IO-Link population is small, check whether a ctrlX I/O module can read IO-Link ISDU parameters before adding a separate master at all.

One safety note belongs here: a written parameter set is machine documentation. A changed switch point or measuring range changes how the machine reacts, so write each value deliberately, read it back from the device, and keep the record with the machine.

The case: a ctrlX CORE with an EtherCAT IO-Link master, proposed as the replacement for the add-on.

Inputs, with sources:

  • Required functions: 5, the list above, from the add-on's published description — the request restated as a checklist.
  • Functions the plain route delivers as designed: 1, parameterization, because ISDU read and write over AoE is documented and working; it runs from PLC code instead of a configurator, but the capability is there.
  • Functions absent: 5 − 1 = 4 — scan recognition, direct project import, project-resident parameter storage, and IODD-driven data interpretation.
  • Bus capability: cyclic port data in the process image, from the master's EtherCAT device documentation.

Rule: a substitute replaces the add-on only when it provides 5 of 5 functions. That is an acceptance rule set by the project, not a vendor limit.

Arithmetic: 5 required − 1 delivered = 4 to cover by procedure. Of those four, interpretation is a one-time job per device (open the IODD, code the scaling), storage becomes a controlled parameter record, and scan recognition and direct import simply do not exist on this route.

Result: 1 of 5. This is an evaluation against documented behavior, not a test result.

Decision: 1 of 5 sits below the 5-of-5 threshold, so this route is a data and parameter path, not the engineering workflow. Commission it when the machine needs data and parameter access, and budget the four procedural covers as engineering hours rather than something a later license will retroactively organize for you.

The decision for each case #

  • You need all five functions on the ctrlX CORE. Not available today. Track the add-on's arrival in the controller's license management and release notes, and if the schedule cannot wait, run that IO-Link engineering on a runtime that provides the target license and hand the ctrlX cyclic data over the fieldbus.
  • You need cyclic data plus parameter access. Take the plain master route from the worked example: 1 of 5 functions, four procedural covers, parameters written and read back per port.
  • You need a few parameters set once at commissioning. Skip the separate master where an I/O module with ISDU access fits, or use the master vendor's own configurator, and file the parameter record with the machine documentation either way.

Questions asked

Can I buy CODESYS IO-Link SL in the store and activate it on my ctrlX CORE myself?

No. It is a single-device license that activates on the CODESYS runtime inside a target which provides it. The ctrlX CORE does not currently offer it through its license management, so a store purchase has no documented activation path on that controller. Re-check the controller's license offering before buying, because the status was under review in March 2024.

Is the CODESYS IO-Link Master license for the EL6224 the same thing?

No. CODESYS IO-Link Master (for EL6224) SL is a separate, device-specific license that drives that one EtherCAT IO-Link master terminal, with activation on a CODESYS Runtime Key or the free CODESYS Soft Key. It does not bring the scan, import, configurator, project storage or IODD processing of IO-Link SL to a ctrlX CORE.

Do I still need IODD files without the add-on?

Yes, but you use them yourself instead of importing them. Open the IODD.xml for each device, read the process-data layout and scaling, and carry those numbers into your PLC code as documented constants. Every scaling value in the project should trace to the IODD revision it came from, so a device swap can be checked against the same file.

Where do device parameters live if they are not stored in the CODESYS project?

In the device, plus the record you keep: a parameter list filed with the machine documentation, PLC code that writes the values at commissioning, or the master vendor's configurator file. Write each value, read it back, and version the record so a replacement device can be restored to identical settings.

What changes for me if ctrlX provides the license later?

Then one single-device license per controller buys the whole workflow: scan recognition, direct import, configurators, project-resident parameters and IODD-based processing arrive together. Confirm the exact ctrlX CORE configuration and its runtime version in the release notes first, because target support is the first thing the license checks.

Keep reading

  • Troubleshooting

    Fix ctrlX PLC license invalid exceptions on download

    The CmpApp invalid-license-metrics exception has two separate causes: a missing CODESYS IO-Link entitlement, shown by a demo-mode line in the log, or a known symbol-configuration bug cleared by Online > Reset Origin before the download. No Data Layer access license exists to buy.

    PLC programming

  • How-to

    Route an IO-Link master to a ctrlX CORE over EtherCAT

    Install the AL1930 ESI in ctrlX I/O Engineering, set channel one to the sensor's documented bytes (4 for a TS2289, 2 for a TP3231), deactivate unused slots, and download until the master reports OP. Cyclic TxPDO bytes feed the PLC, CXA_EthercatMaster blocks read vendor and product ID over AoE with the master NetID, and EoE routing for ifm Moneo or LR clients depends on the master firmware.

    PLC programming

  • Troubleshooting

    Why an IODD file will not plug into a PROFINET IO-Link master

    Nothing is wrong with the IODD. PROFINET never consumes it as a pluggable module: the master's GSDML defines every module under Plug Device, and the IODD only describes the sensor on the IO-Link side. Configure the master's port modules or its webserver communication table, map the cyclic bytes in the PLC, and keep the IODD for parameter work.

    Industrial networks