Selection guide
Choosing how an S7 PLC talks to a Mitsubishi Q or AnS PLC
Short answer
Yes — the link exists on every generation. Put Modbus TCP (QJ71MT91) or Modbus RTU (QJ71MB91) against a Mitsubishi Q series PLC, PROFIBUS master or slave against an AnS or QnAS because those generations had no Modbus modules, and a protocol-converting gateway where the two sides share no interface.
On this page
- Can an S7-300 or S7-400 exchange data with a Mitsubishi PLC?
- Which protocol should I use with a Mitsubishi Q series PLC?
- Which protocol works with an AnS or QnAS PLC?
- What does the Siemens side need for Modbus RTU or Modbus TCP?
- How many words fit in one Modbus request?
- When is a gateway the better choice?
- How do I verify the word transfer after commissioning?
- Questions asked
Yes, and the choice follows the Mitsubishi generation, not the Siemens one. A Q series PLC gives you Modbus TCP (QJ71MT91), Modbus RTU (QJ71MB91), PROFIBUS and Mitsubishi's own Ethernet protocol; an AnS or QnAS gives you PROFIBUS only, because those generations never had Modbus modules. When the two sides share none of that, a protocol-converting gateway or a dual-protocol operator panel bridges them. This article walks the decision in the order you meet it: platform, protocol, Siemens-side hardware, block size, gateway, verification.
Can an S7-300 or S7-400 exchange data with a Mitsubishi PLC? #
Yes: an S7-300 or S7-400 can exchange word blocks with a Mitsubishi Q series PLC over Modbus TCP, Modbus RTU or PROFIBUS, and with an AnS or QnAS over PROFIBUS; a gateway covers every other combination.
The decision has three inputs: which Mitsubishi platform you face, what the Siemens rack already holds, and whether the two sides share a protocol. Work them in that order and the table below settles it.
| Mitsubishi platform | Interfaces documented for it | What the S7 side needs | Use it when |
|---|---|---|---|
| Q series | Modbus TCP via QJ71MT91, Modbus RTU via QJ71MB91, PROFIBUS master or slave, Mitsubishi's own Ethernet protocol | Ethernet path plus Modbus TCP function blocks, CP341 or CP441 with the licensed Modbus driver, or an existing PROFIBUS master | The link is new (Modbus TCP), PROFIBUS cable already reaches the cabinet, or the run must be serial |
| AnS / QnAS | PROFIBUS master or slave only; no Modbus modules existed for this generation | A PROFIBUS master interface in the S7 rack | Every AnS or QnAS job, because there is no Modbus alternative |
| Any, or mixed sides | None shared | Only the interface the gateway uses | A data station or dual-protocol panel bridges MPI/PROFIBUS to Ethernet, RS-232 or Modbus |
Mitsubishi's own Ethernet protocol is neither PROFINET nor EtherNet/IP, so no Siemens CPU speaks it directly — that fact alone pushes most links toward Modbus. For the protocol-level trade-offs behind these rows, how to choose between Modbus, Profibus and CANopen works the same decision protocol by protocol.
Which protocol should I use with a Mitsubishi Q series PLC? #
Modbus TCP, using the QJ71MT91 interface module, is the default for a new link: it runs on the plant Ethernet, and the S7 side needs function blocks rather than a licensed serial driver.
The QJ71MT91 is Mitsubishi's dedicated MODBUS/TCP interface module for the Q rack, documented in its own manual; the QJ71MB91 does the same job on serial Modbus. Choose RTU only when no Ethernet reaches the Mitsubishi cabinet or the run must stay RS-485 two-wire. Choose PROFIBUS when a segment already exists between the two cabinets — adding one slave to a working S7-400 network beats pulling new Ethernet through the plant.
Leave Mitsubishi's own Ethernet protocol out of the link plan: it belongs to Mitsubishi toolchains, and its only consumer on your side is a gateway.
If the machine record says "QO6", that string matches no Mitsubishi type code as written. Read the nameplate: a Q06 designation is Q-series CPU territory, so if that is what is installed, the Q-series row above applies.
Which protocol works with an AnS or QnAS PLC? #
PROFIBUS — master or slave — is the interface that generation actually shipped; AnS and QnAS had no Modbus communication modules, so planning anything else on the PLC side wastes engineering time.
Set the Mitsubishi card as a PROFIBUS slave and let the S7 master it; reverse the roles only if that machine already owns the segment. One older field report mentions an A-series Modbus slave from decades back, but it is unconfirmed and nothing in the current lineup covers those racks — do not design around it.
Budget real configuration time: a PROFIBUS card needs its GSD imported, the station addressed and the consistent-data handling programmed before one word moves. Field experience consistently rates Modbus easier to commission, but on this generation Modbus does not exist, so that effort is the price of the machine you have. Once the segment carries traffic, intermittent PROFIBUS dropouts on an S7-400 network become their own fault class and are worth a separate look.
What does the Siemens side need for Modbus RTU or Modbus TCP? #
For Modbus RTU, a CP341 or CP441 serial communication processor plus its separately licensed loadable Modbus driver; for Modbus TCP, a standard Ethernet path and Modbus function blocks in the S7 program.
The RTU driver is a licensed package ordered per communication processor — buy it with the card, because without it the port moves raw serial data only. The questions that decide the 300-side hardware are worked through in choosing a CP-341 or gateway for an S7-300 Modbus RTU slave, and they apply to the master role here as well.
For Modbus TCP, the licensing of the function-block package is not established by the module documents: confirm what it permits before you copy one block set onto both the S7-300 and the S7-400.
Keep the S7 as the single Modbus master or client, polling the Mitsubishi as slave or server, so the update rate lives where the data is consumed.
How many words fit in one Modbus request? #
One read moves up to 125 holding registers and one write up to 123 registers, so a 100-word block needs exactly one request, not one per word.
Worked example, DB100 to D1000. The S7-400 holds a 100-word block in DB100 (DBW0 through DBW198); the Q series must see it in D1000 through D1099, with the QJ71MT91 as the Modbus server.
- Payload: 100 words × 2 byte/word = 200 byte.
- Registers: 200 byte ÷ 2 byte/register = 100 holding registers at consecutive 4x addresses.
- Requests: function 16 writes at most 123 registers, and 100 ≤ 123, so one request per update. A 150-word block would split 123 + 27 into two.
- Load at a 100 ms poll: 200 byte × 10 update/s = 2000 byte/s of payload — negligible on switched Ethernet.
The same register limits apply to Modbus RTU, but there the line speed becomes the limit. Illustrative: at 19.2 kbit/s with 10 bits per framed byte, one 200-byte block takes 200 × 10 = 2000 bit ÷ 19200 bit/s ≈ 0.104 s, so fewer than 10 updates per second is the ceiling — Modbus TCP wins whenever the block is this size and Ethernet exists.
Decision from the numbers: any block up to 123 words is one request on either transport; above that, split at a register boundary and keep the split fixed so the register map never moves.
When is a gateway the better choice? #
When the two sides share no common interface — an AnS on PROFIBUS facing an S7 with no free slot for a communication processor, or a machine whose program you may not touch — put a protocol-converting data station or dual-protocol operator panel between them and map the words across.
The documented arrangement talks MPI or PROFIBUS to the Siemens side and Ethernet, RS-232 or Modbus to the Mitsubishi side, then maps word blocks between the two. If the machine needs an operator panel anyway, a panel carrying both driver sets does the transfer as a second job: one device, two functions.
A PC-based bridge is the same idea in software: protocol converter or OPC UA middleware running on an industrial mini PC mounted beside the controller. Verify three things before committing to any gateway: a listed driver for your exact CPU pair — the older Mitsubishi protocols are where gateway lineups differ — the tag capacity per map, and the fastest update it will actually hold.
How do I verify the word transfer after commissioning? #
Map one defined source block to one defined destination block, force a known pattern, and confirm value, order and update time on both sides before you call the job done.
- Write 0x1234 into the first word and 0x4321 into the last; if the far side reads 0x3412, the byte order differs — swap on one side only.
- Walk a rising count through the block to catch an off-by-one: Modbus register addressing starts at zero under the 4x label, and that single offset is the classic mapping fault.
- Measure end-to-end update time at the poll rate you configured, and repeat the test in the reverse direction if words flow both ways.
- Pull the cable: the consuming logic must see a communication fault flag, mark the data stale, and recover on reconnect without a restart.
For the destination numbering, how Q series PLC addressing works for I/O and analog modules sets out the device numbering you are mapping into.
Keep safety functions off this link: an emergency stop that depends on a polled word inherits the poll interval and a broken cable, so the stop chain stays hardwired.
Questions asked
Does a Mitsubishi Q series PLC speak PROFINET or EtherNet/IP?
No. The documented Q series interfaces are Modbus TCP through the QJ71MT91, serial Modbus through the QJ71MB91, PROFIBUS, and Mitsubishi's own Ethernet protocol. If the Siemens side must stay PROFINET or EtherNet/IP, put a gateway between them rather than waiting for the PLCs to agree.
Is the Modbus driver for the CP341 or CP441 included with the module?
No — the Modbus RTU driver is a separately licensed loadable package, one per communication processor. Order it with the CP; without it the port passes raw serial data only. For Modbus TCP the function-block route avoids that license, but confirm the package's own terms before copying it onto both controllers.
Did the A or AnS series ever get a Modbus module?
One field report from that era mentions an A-series Modbus slave, but no current documentation supports it and nothing in the present lineup covers those racks. Treat PROFIBUS as the only native path for AnS and QnAS, and use a gateway if the Siemens side cannot host a PROFIBUS master.
Can one gateway move words in both directions?
Yes. A data station or dual-protocol panel maps tags from Siemens to Mitsubishi and back over the same pair of drivers. Verify word order separately in each direction, because the two sides can disagree about byte order and a swap fixed one way reappears in the other.