IMDHMIControls LibraryShop main store

How-to

Bridging a MicroLogix 1400 to a PLC-5 through Kepware

SCADA and data logging Published 8 min read

Short answer

Yes. Add both controllers to one KEPServerEX project and use an Advanced Tags link tag to copy each value from the PLC-5 tag to the MicroLogix 1400 tag; the server becomes the bridge. Keep it as a status and setpoint path, prove it with a heartbeat counter, and never run an interlock over it.

On this page
  1. What a link tag does and what it costs
  2. Check both controllers before you build
  3. Reserve one word in each controller
  4. Build the link tags
  5. Size a heartbeat, not a promise
  6. Prove the path before you trust it
  7. Faults the test client shows
  8. The decision for your case
  9. Questions asked

Yes — a MicroLogix 1400 on Ethernet and a PLC-5/60 on DH+ can share data, and the bridge is not in either controller. Put both devices into one KEPServerEX project and let an Advanced Tags link tag read a word from one controller and write it to the other. The DCS connection to the PLC-5 keeps running untouched, because all the new work lives in the server you already operate, the one element on the plant that talks to both networks. Treat the result as a status and setpoint path with a PC in the middle, and prove it with a heartbeat counter before anyone relies on it.

A link tag runs inside the server runtime. It reads the source tag on one device and writes the value to the target tag on the other, and neither controller learns that the other exists. Each PLC sees only ordinary reads and writes against its own data table — the same traffic a SCADA client produces, as laid out in how a SCADA client reads a small PLC over EtherNet/IP.

Three costs decide where this architecture is allowed:

  • The PC joins the signal path. If the runtime stops, the PC reboots or either channel drops, the copy stops and the target word keeps the last value written.
  • The timing is not deterministic. Latency is the sum of the DH+ scan, the Ethernet scan and the link update cycle, so it moves with server load.
  • The target must be writable. A word the ladder rewrites every scan fights the server, and the value flickers or never settles.

A message instruction cannot replace this either: what a DF1 message instruction needs to link two PLCs is a network both ends share, and Ethernet plus DH+ offers none. That absence is the whole reason the server does the moving.

The host PC matters too. Beside the panel, whatever machine the site already runs will do; when the bridge belongs inside the cabinet as a permanent gateway next to the controller, an industrial mini PC is the hardware built for that duty.

Check both controllers before you build #

Work in this order, because the DH+ side is already proven and must stay that way.

  1. Confirm the DCS still reads its PLC-5 tags with good quality in the server's test client. If it does, the DH+ channel is done and nothing on it changes. That path carries its own constraints, set out in what decides a PLC to legacy DCS communications link, and they are already settled on this installation.
  2. Add the MicroLogix 1400 as a second channel and device on its Ethernet address, using the driver family for that controller, and read one element in the test client. Bad quality means a wrong address, a wrong driver choice or a network fault; fix that first, because no link tag can rescue a channel that cannot read.
  3. Note the server build before you configure anything. An older install such as KEPServerEX v5.8.109 shows different option and menu names than current manuals describe, so match every step that follows to the manual for the release installed.

Reserve one word in each controller #

Pick the source in the PLC-5: a spare integer word that only its own ladder writes, for example N7:50 — use a file you genuinely control, the address is an illustration. Reserve the destination in the MicroLogix program the same way, for example N7:20, in a data file nothing else touches, and make its server tag read/write. Keep the data types identical end to end; converting bits to words or the reverse belongs in ladder, not in the server. The return direction needs the same pairing: a status or pressure word owned by the MicroLogix alone, and a spare landing word in the PLC-5. One writer per word, both directions, is what prevents flicker later.

  1. Create a tag on the PLC-5 device for the source word and confirm good quality in the test client.
  2. Create a read/write tag on the MicroLogix device for the destination word and confirm a test write from the client lands in the controller's data table — use the spare word, never a live value.
  3. Verify the Advanced Tags option is installed and licensed on this release. If the entry does not exist in the project, the option is missing, and the fix is licensing it, not more address changes.
  4. Add a link tag. Set the source to the PLC-5 tag and the target to the MicroLogix tag, and enable on-change updates plus the periodic refresh the option offers — the refresh is what re-writes the target after a controller power cycle. The linking page of the Advanced Tags manual for your release carries the exact settings, and their names move between versions.
  5. Add a second link tag for the return word with source and target reversed. Every link is one-way, so a two-way path is a pair of links.
  6. Save and run the project, then watch both tags in the test client.

Size a heartbeat, not a promise #

The remote word must never be trusted on its own. Give the PLC-5 a free-running timer that increments a counter word, copy that counter across on its own link tag, and let the MicroLogix revert the filter bank to local control when the count stops moving.

One safety note: never carry a trip or interlock over this link. ISO 13849-1 expects a safety function to be one deterministic chain from sensor to final device, specified and validated as a whole, and a best-effort copy made by a PC application is not part of any chain that passes validation.

Worked example, with the design inputs stated as choices. Set the PLC-5 timer period to 500 ms and scan the heartbeat tag on both devices at 500 ms. Worst-case age of the last copy at the MicroLogix is then timer period + PLC-5 read scan + MicroLogix write scan = 500 ms + 500 ms + 500 ms = 1500 ms. Preset the loss timer at twice the worst-case age: 2 × 1500 ms = 3000 ms. The decision follows from those inputs: a healthy link can legitimately show a 1500 ms gap between count changes, so a shorter preset trips good traffic, while a genuinely lost server drops the bank to local mode in 3000 ms — two missed counts plus margin. Change any period and recompute the preset as twice the sum of the three periods; toggle a value once and timestamp both ends to compare the real age with the paper figure, and widen the preset if the measured age is larger.

Prove the path before you trust it #

  • Move the PLC-5 source to one known value, then to a different one, and watch the MicroLogix word in its data table. The target must follow every change; a single update proves only that on-change firing works.
  • Power-cycle the MicroLogix and confirm the value returns once the device reconnects. If it stays at zero or holds the old number, the periodic refresh is off.
  • Stop the runtime, change the source, restart, and confirm the target catches up. Then leave it running for an afternoon before anyone relies on it.
  • Force the failure on purpose: stop the runtime and watch the bank revert to local mode at the loss timer preset. A link you have never seen fail is not commissioned.
  • Compare DCS scan times before and after commissioning; the heartbeat rides the same DH+ token path the DCS uses.

Faults the test client shows #

Symptom Likely cause What to do
MicroLogix tags read bad quality Wrong address, wrong driver on the channel, or a network fault Fix the channel first; no link works over a channel that cannot read
Advanced Tags entry missing from the project Option not installed or not licensed on this release Check installed components and the license; add the option for your build
Link created, target never changes Source quality bad, or the target address is wrong or read-only Check quality on both tags and write access on the target
Target moves once, then stops On-change firing only, and the source has stopped changing Expected behavior; rely on the periodic refresh and the heartbeat
Value arrives, ladder ignores it Data type or file mismatch, or the ladder overwrites the word every scan Match the types and give the word a single owner

The decision for your case #

Sharing status, mode requests and setpoints between the two controllers: build it now on the server you already run — two one-way link tags, the heartbeat counter copied on its own link, and the loss timer preset at twice the worst-case age your scan rates produce.

Anything safety-graded, or any interlock: not over the server, without exception. Hardwire it or carry it on a validated deterministic network with the trip logic in the receiving controller, and let this link carry at most a request.

The Advanced Tags option absent from your release: license and install it for that build; until then the server has no bridge. If you would rather take the PC out of the path entirely, the hardware route is a gateway module in the PLC-5 chassis — the MVI71-DFNT PLC-5/60 Ethernet passthrough configuration covers that card-level route. The controller-level version of the same idea, a bridge between DH+ and the Logix Ethernet world, is walked through in reaching PLC-5 and SLC 500 data through a ControlLogix DH+ bridge.

Questions asked

Can the bridge run on the same KEPServerEX project the DCS uses?

Yes. One project holds both channels, and adding the MicroLogix device does not disturb the DCS device. Plan the Advanced Tags install as a small window though: if enabling the option restarts the runtime on your release, the DCS reads stop for that window. Do it deliberately and confirm every DCS tag is back to good quality before leaving the desk.

Why does the MicroLogix hold its last value when the server stops?

The link tag is only a copy made inside the server runtime, so the last completed write stays in the MicroLogix word and nothing in the controller knows the source stopped. That is the designed failure mode, and it is why the receiving ladder watches the heartbeat counter and reverts to local control on a timeout instead of trusting the word itself.

How much traffic does a link tag add to the DH+ network?

One heartbeat word scanned at 500 ms adds two short reads per second to the DH+ token path, which no DCS will notice. Dozens of link tags scanned at aggressive rates on a long DH+ run are what push DCS scan times out, so scan each link at the slowest rate the application tolerates and compare DCS scan times before and after.

What if the Advanced Tags option is not on this server?

Then the runtime cannot bridge the devices, because the copy runs inside the server and nowhere else. Check the installed components and the license for that release first; the option is licensed per installation and the vendor confirms what a specific build supports. Until it is enabled, the choices are licensing it or moving the bridge into gateway hardware in the PLC-5 chassis.

Keep reading

  • Troubleshooting

    Connect SCADA to an SLC 5/03 and MicroLogix 1500

    None of the three listed drivers will work: ControlLogix and CompactLogix are different controller families, and the MicroLogix 1100/1400 connection is Ethernet to models that have an Ethernet port. Your SLC 5/03 and MicroLogix 1500 LRP are serial-only, so connect through an OPC server with a serial DF1 or DH-485 driver, or a protocol-aware gateway. Put both controllers on one DH-485 network and bridge it once.

    SCADA and data logging

  • Troubleshooting

    Commissioning CP1L Host Link serial reads to SCADA

    CX-Programmer going online proves only the programming path, not the SCADA read. Set the CP1L serial port to Host Link, enter its unit number (0 to 31) as the driver's device address, match baud, data bits, parity and stop bits, prove the cable end to end, and free the computer port of other software. Read one known word before adding tags: a timeout means no valid reply arrived; a PLC protocol error proves the link works.

    SCADA and data logging

  • Selection guide

    Choosing PLC to SCADA communication over long distances

    For PLC-to-SCADA communication over long distance, choose the transport by reach and connection behavior: fiber Ethernet for a continuous long link (one span rated 2 km), RS-485 where serial fits, extenders or radio on existing pairs, dial-up or leased-line modems on phone service. Direct copper Ethernet fails at 100 m per segment; the SCADA driver or OPC service, not the PLC's ASCII modem commands, carries the protocol.