Short answer

Yes, from the controller: put the Micro820 in Program mode and run the memory card backup command from Connected Components Workbench, and the controller writes a loadable image to the microSD card. Use a Class 6 or Class 10 SDSC or SDHC card, FAT16 or FAT32, up to 32 GB. The card image restores the controller; it does not replace archiving the CCW project.

On this page
  1. The card carries a controller image, not your project
  2. What card the Micro820 accepts
  3. Qualifying a 16 GB Class 10 SDHC card for the Micro820 slot
  4. Before you touch the controller
  5. The backup procedure, step by step
  6. Prove the backup recovers
  7. What goes wrong
  8. The decision
  9. Questions asked

Yes — from the controller, not from the card slot. The Micro820 writes its own backup when you run the memory card backup command from Connected Components Workbench (CCW) with the controller in Program mode. The microSD slot does nothing until that command runs, and copying the CCW project folder onto a card with a PC does not create a restorable image. The documented sequence for your case is: download the edited program, run the controller-to-card backup, keep that card as the recovery copy for this controller. Archive the CCW project separately, because the card restores the controller and nothing else. Below: the card the controller accepts, the procedure step by step, and how to prove the backup recovers.

The card carries a controller image, not your project #

The slot exists for exactly this job: the installation instructions 2080-IN009B-EN-P describe the microSD card as primarily used for project backup and restore. Backup and restore are the two directions of one transfer. Backup writes the controller's current application to the card. Restore loads a stored application from the card into the controller, overwriting what it runs.

What the card does not hold is your CCW project. Comments, tag descriptions and the program structure stay in the project file on the engineering PC. An upload back from the controller does not close that gap, because uploading a PLC program is not full source recovery: what comes back lacks the documentation the project file carries. Copying the CCW project folder to the card is the other dead end — the controller cannot load a project folder, only the image its own backup command writes.

What card the Micro820 accepts #

Documented support for the slot covers Class 6 and Class 10 cards, types SDSC and SDHC, formatted FAT16 or FAT32, with a maximum capacity of 32 GB. The class and type are printed on the card label; the file system is whatever the card was formatted with, which a PC will show you before you trust it. An SDXC card is outside the documented support on capacity alone, before format even comes up. Choose the card against that list rather than reformatting whatever is in the drawer.

Qualifying a 16 GB Class 10 SDHC card for the Micro820 slot #

Take an example card from the drawer and run four checks before it goes near the controller.

Inputs, and where each comes from:

  • Card capacity: 16 GB, read from the card label.
  • Speed class: Class 10, read from the label.
  • Card type: SDHC, read from the label.
  • File system: FAT32, set when the card was formatted and shown by the PC's file explorer.
  • Controller limits: Class 6 or Class 10, SDSC or SDHC, FAT16 or FAT32, capacity up to 32 GB — all from the Rockwell Automation support answer on Micro820 microSD card support.

The rule, in words: the card must pass all four checks against the controller's documented support. Capacity is the one check no later step can fix — formatting changes the file system, never the size of the card.

The arithmetic:

  • Capacity: 32 GB − 16 GB = 16 GB of headroom, and 16 GB ≤ 32 GB, pass.
  • Class: the label's speed class sits in the documented pair, pass.
  • Type: the card type is one of the two documented, pass.
  • File system: FAT32 is a documented format, pass.

Result: the card qualifies on all four checks.

Decision: use this card for the backup. A 64 GB card fails the first check — 64 GB − 32 GB = 32 GB over the limit — and no class rating or reformat rescues it; any card above the documented ceiling is out, whatever else the label says.

Before you touch the controller #

  • Save the CCW project with the changes you downloaded and copy it to the engineering archive. This comes first; everything after it protects the controller, not the source.
  • Record the controller's catalog identification, its firmware revision and the CCW version. They go on the card label later, and they decide which revision of the Micro820 user manual, 2080-UM005H-EN-E, applies.
  • Confirm the CCW connection is to the intended controller. Check the identity shown online against the unit in front of you, not against a familiar project name.
  • Look at what is already in the slot. A card found there may carry an older recovery image; read its label before you overwrite anything.
  • Plan the stop. The documented backup runs in Program mode, so the machine is down for the write. Tell the operator before, not during.

The backup procedure, step by step #

  1. Save the CCW project and file a copy in the archive, with the controller identification and firmware revision noted beside it.
  2. Install the card in the slot as the installation instructions show.
  3. Switch the controller to Program mode from CCW. The program stops executing and the outputs go to their configured off state — this is the interruption you scheduled.
  4. With CCW connected to that controller, select the controller Micro820, then Memory Card, then Backup to Memory Card.
  5. Check the direction before you confirm: this command writes from controller to card. Loading the card's contents back into the controller is the restore, and it overwrites the running application.
  6. Let the write finish. The operation ends with a completion message from CCW; if it ends with an error instead, write the text down exactly before trying anything else.
  7. Leave the card seated while the write runs. Pulling it mid-transfer leaves an image you cannot trust.
  8. Return the controller to Run mode and hand the machine back.
  9. Label the card with the date, the controller identification, the firmware revision and the application revision, and store it with the machine.

Prove the backup recovers #

Check the result at two levels: created, and recoverable.

Created means the write ended with the completion message, not an error, and the card carries today's backup under its own label. That is the minimum before you leave the outage window.

Recoverable means the card has completed a load. The documented backup and restore sequence runs download to the controller, backup to the card, then load program from the card — that load is your restore. On a planned stop, run it, let the controller come back up, and compare the running application against the archived project in CCW before the machine returns to production. If today's window has no time for the round trip, schedule the restore test for the next one and treat the card as unproven until then. The round trip also proves the card, the slot and the image on this exact unit.

What goes wrong #

Symptom Likely cause Fix
Controller does not recognize the card Card outside the documented support, wrong file system, or poor seating Use a card from the supported list; reseat it per the installation instructions
Backup command unavailable Controller still in Run mode, or CCW is connected elsewhere Switch to Program mode; verify the connection identity
Write fails partway Card removed during the write, or a failing card Rerun with a qualified card; record the error text exactly
Card restores an old program Card holds an earlier backup and was never refreshed Run a fresh backup after every download; date the label

The decision #

For the case in hand — changes made in CCW and downloaded — do both, today, in this order: archive the CCW project, then run the controller-to-card backup in Program mode and label the card. Two copies, two jobs: the project keeps the source editable, the card keeps the machine recoverable.

If nothing was edited and the goal is protecting a running machine: one fresh card backup after every download, labeled and stored with the machine. A card older than the last download is not a backup of what is running.

If the job is replacing or cloning a controller: the same card mechanism is the documented path — back up the source, load the card on the target — with the same controller model and both firmware revisions recorded.

If no supported card is on hand, do not substitute the project folder; the CCW archive is the only copy until a qualified card arrives. On older controllers without a card slot the equivalent discipline is an upload before anything changes — one such procedure is in back up an SLC 500 program by upload before you lose it.

Questions asked

Can I reformat a 64 GB SDXC card and use it?

No. Formatting changes the file system, never the capacity, and that card sits above the documented maximum, so the controller is not supported with it however it is formatted. SDXC cards also commonly ship with the exFAT file system, which the Micro820 does not list. Use an SDHC card within the documented limit instead.

Do I have to stop the machine to run the backup?

Yes. The documented procedure switches the controller to Program mode before the backup command, and in Program mode the program stops executing and the outputs go to their configured off state. Schedule the stop, run the write, then return the controller to Run mode. The card write is one operation; the mode change is what costs the process interruption.

Does the card backup include my CCW project comments?

No. The card carries a controller-loadable image of the application. Project comments, tag descriptions and the program structure you edit live only in the CCW project file on the engineering PC, so archive that file separately, with the controller's catalog identification and firmware revision noted next to it. Neither copy substitutes for the other.

Can I use the same card to clone a second Micro820?

Yes. The controller-to-card backup is the first half of the documented cloning procedure: back up the source controller, then load the card into the target. Keep the target the same controller model, and record both firmware revisions, so the restored application runs on the combination it was verified against. Label the card as a clone image so nobody refreshes it by mistake.

Keep reading

  • Selection guide

    Migrating a MicroLogix 1500 machine to a current PLC

    Quote CompactLogix as the baseline for the rebuild: Rockwell's migration reference gives the MicroLogix 1500 two documented destinations, MicroLogix 1400 or CompactLogix 5370 (L1/L2), and a low-volume machine rebuild does not justify the Micro850 route. Take the Micro850 only for high build volume, after the 11 uncovered inputs, serial Modbus, the drive interface and a trial CCW import are verified.

    PLC programming

  • How-to

    Back up an SLC 500 program by upload before you lose it

    An SLC 500 backup is an upload: read the program out of processor memory into a new RSLogix 500 offline file over a working RSLinx driver, save that file, then run a compare against the processor to prove the copy matches. Work the sequence below on the live processor and never download or clear memory to get there.

    PLC programming

  • Selection guide

    Is MicroWin32 suitable for complex S7-200 PLC programs

    MicroWin32, the S7-200 environment sold as STEP 7 Micro/WIN, carries a complex program when the logic is built as named, parameterized subroutines over a documented memory map. It is the wrong tool when the design needs compile-time constants, code macros, whole-project source export, or many small interrupt routines. Build one representative sequence, one reused function, and the real interrupt count first; the prototype, not the I/O count, decides.

    PLC programming