Trace the signal.

Start at the sensor, follow the input through the PLC and check what the operator sees. Field notes cover the points where those readings disagree.

Operator station hardware →

Controllers and I/O

1769-IF8 shows no input readings on a MicroLogix 1500

A 1769-IF8 that shows no readings on a MicroLogix 1500 almost always has its channels disabled in the module configuration, or a channel set for current on a voltage transmitter. Enable each channel, match the input type to the transmitter, then watch the live input data before touching any logic.